How do you properly connect or wire a transformer with the voltage code T2F?
Issue:
How is a transformer with the voltage code T2F wired or connected?

Product Line:
Transformer

Environment:
T2F transformers

Resolution:
For 480v delta to 208/120V 3 phase 4 wire.
Connect 480v to H1, H2, H3, and cap off all other H wires individually.
For 208/120V  connect X1, X2, X3 to the load and X0 to the neutral. See wiring diagram below.
wire wire1




Schneider Electric USA

How do you properly connect or wire a transformer with the voltage code T2F?
Issue:
How is a transformer with the voltage code T2F wired or connected?

Product Line:
Transformer

Environment:
T2F transformers

Resolution:
For 480v delta to 208/120V 3 phase 4 wire.  
Connect 480v to H1, H2, H3, and cap off all other H wires individually.  
For 208/120V  connect X1, X2, X3 to the load and X0 to the neutral. See wiring diagram below.
wire wire1




 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.