Search FAQs
Why does my ATS22 S6U not run when 120VAC is closed to LI1 and LI2?
Issue:
My ATS22 S6U will not run when 120VAC is at LI1 and LI2.
Product line:
ATS22 Soft Starters
Environment:
S6U versions, All serial numbers.
Cause:
Incorrect wiring.
Resolution:
On the S6U version, it is necessary to tie Neutral not only to CL2, but also to the COM terminal.
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: