On the Iso-Gard Line Isolation Monitor IG6, What does EF Extreme Fault indicate?
Issue:
How to troubleshoot the Extreme Fault indicator EF on a IG6 LIM?
Product Line:
LIM, Line isolation Monitor
Environment:
IG6M, IG6
Cause:
Display shows Extreme Fault
Resolution:
There are some circuits that are not always compatible with the LIM in the panel. To find those circuits, turn each breaker off one at a time and let the LIM recycle until they find the circuit that has the issue. If that does not work they will need to replace the LIM.
How to troubleshoot the Extreme Fault indicator EF on a IG6 LIM?
Product Line:
LIM, Line isolation Monitor
Environment:
IG6M, IG6
Cause:
Display shows Extreme Fault
Resolution:
There are some circuits that are not always compatible with the LIM in the panel. To find those circuits, turn each breaker off one at a time and let the LIM recycle until they find the circuit that has the issue. If that does not work they will need to replace the LIM.