{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
How can I install a EStop on an Altistart softstarter?
Issue:
Install EStop on an Altistart softstarts.

Product Line:
ATS48  ATS22  ATS01

Environment:
All series

Cause:
Customer would like the softstart to shut down (stop) on any external fault trips.

Resolution:
Series the external fault contacts (normally closed) with the run / stop command to open on a external fault.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: