Issue:
Do PQ busway plug in units include Class R fuse clips?
Product Line:
Busway Plug in units
Environment:
I-line, I-lineII PQ busway units
Cause:
N/A
Resolution:
No, they are ordered as separate items. The units are supplied with Class H fuse clips as standard for 600A and below. 800A and above include class L fuse clips and do not accept any other fuses.