How do you wire a 9001K or 9001SK speed potentiometer?
Issue:
Customer is trying to find information on how to install a 9001K2108 Speed pot.

Product line:
Push Buttons and Operator Interface

Environment:
9001K, 9001SK potentiometer

Cause:
Wiring

Resolution:
See the attached Instruction bulletin for the Speed pot.  Typical speed pot wiring is Positive, Negative and Wiper contacts.  Positive goes to the power supply, typically +10VDC.  The Negative goes to the Common terminal. The Wiper is the output signal.

For the 9001 series, we use Terminals 1 (Positive), 2 (Wiper) and 3 (Negative).

If you find the speed pot is not outputting the correct voltage, try reversing terminals 1 and 3 (Negative and Positive).

Schneider Electric USA

Attachment(s)
9001K21 K20 speed pot wiring.pdf [726.04 KB]
How do you wire a 9001K or 9001SK speed potentiometer?
 Issue:
Customer is trying to find information on how to install a 9001K2108 Speed pot.

Product line:
Push Buttons and Operator Interface

Environment:
9001K, 9001SK potentiometer

Cause:
Wiring

Resolution:
See the attached Instruction bulletin for the Speed pot.  Typical speed pot wiring is Positive, Negative and Wiper contacts.  Positive goes to the power supply, typically +10VDC.  The Negative goes to the Common terminal. The Wiper is the output signal. 

For the 9001 series, we use Terminals 1 (Positive), 2 (Wiper) and 3 (Negative).

If you find the speed pot is not outputting the correct voltage, try reversing terminals 1 and 3 (Negative and Positive).

Schneider Electric USA

Attachment(s)
9001K21 K20 speed pot wiring.pdf [726.04 KB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.