Issue:
Can the Process Drive be used on a different types of 3 phase power connectoins?
Product Line:
Process Drive
Environment:
All
Cause:
IT system
Ungrounded system
Corner grounded delta
Resolution:
Yes. With any of these systems the internal EMC Filter must be disconnected according to the instructions in the Installation Manual.

ATV600 Installation manual link: https://www.se.com/ww/en/download/document/EAV64301/
ATV900 Installation manual link: https://www.se.com/ww/en/download/document/NHA80932/