Issue:
How can I adjust the speed from the jog dial on the drive?
Product Line:
Altivar ATV Process Drive
Environment:
ALL
Cause:
Programming Wiring
Resolution:
To do the same as ATV312 after pressing Mode key.
ConF > FULL > CtL >
Fr1 = A1U1
CHCF = SEP (hold 2s)
Cd1 = tEr
ESC back to RDY
You can now press Enter (Dial) 3x to adjust the speed
How can I adjust the speed from the jog dial on the drive?
Product Line:
Altivar ATV Process Drive
Environment:
ALL
Cause:
Programming Wiring
Resolution:
To do the same as ATV312 after pressing Mode key.
ConF > FULL > CtL >
Fr1 = A1U1
CHCF = SEP (hold 2s)
Cd1 = tEr
ESC back to RDY
You can now press Enter (Dial) 3x to adjust the speed
Released for:Schneider Electric USA



