{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Example of script to check if another process is running
DISCLAIMER

This sample program is intended to demonstrate one or more programming functions or methods and is presented as programming example only. Schneider Electric assumes no liability for the use or application of this example program or any portion thereof.


This is an example of a mimic script to check if a particular process is running. When execute, an input box would be displayed prompting the user to enter the full name of the process to be checked. For example, for Internet Explorer, one needs to enter "iexplore.exe" (without the quotation marks) into the input box.

Sub CheckProc

Dim i
Dim strComputer
Dim FindProc

strComputer = "."

FindProc = inputbox("Enter process name","Information required")

Set objWMIService = GetObject("winmgmts:" _
    & "{impersonationLevel=impersonate}!\\" & strComputer & "\root\cimv2")
Set colProcessList = objWMIService.ExecQuery _
    ("Select Name from Win32_Process WHERE Name LIKE '" & FindProc & "%'")

If colProcessList.count>0 Then
    msgbox (FindProc & " is running")
Else
    msgbox (FindProc & " is not running")
End if 

Set objWMIService = Nothing
Set colProcessList = Nothing

End Sub

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: