Replacement Components for Surgelogic™ QED Switchboard IMA Surge Protective Devices
Issue:
What are the replacement components for QED Switchboard IMA series Surge Protective Devices?

Product Line:
Surge Protective Devices (SPDs)

Environment:
QED Switchboard Type IMA surge protective devices.

Cause:
Replacement or Repair Parts

Resolution:
To determine the correct Replacement parts to purchase for your QED Switchboard Type IMA series Surge Protective Devices (SPDs), see the Replacement Component Selector Table below. An example of a typical product label and catalog number is at the end of this article.

Replacement Component Matrix
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS1IMA12B120kAMA1IMA12N/AMA1IMA12TVS60PCKTVS1DSPHC
TVS1IMA12BC120kAMA1IMA12N/AMA1IMA12TVS60PCKTVS1DSPHC
TVS1IMA12B1120kAMA1IMA121N/AMA1IMA121TVS60PCKTVS1DSPHC
TVS1IMA16B160kAMA1IMA16N/AMA1IMA16TVS60PCKTVS1DSPHC
TVS1IMA16BC160kAMA1IMA16N/AMA1IMA16TVS60PCKTVS1DSPHC
TVS1IMA16B1160kAMA1IMA161N/AMA1IMA161TVS60PCKTVS1DSPHC
TVS1IMA24B240kAMA1IMA24N/AMA1IMA24TVS60PCKTVS1DSPHC
TVS1IMA24BC240kAMA1IMA24N/AMA1IMA24TVS60PCKTVS1DSPHC
TVS1IMA24B1240kAMA1IMA241N/AMA1IMA241TVS60PCKTVS1DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS1IMA32B320kAMA1IMA16 (2 Modules Required)N/AMA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA32BC320kAMA1IMA16 (2 Modules Required)N/AMA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA32B1320kAMA1IMA161 (2 Modules Required)N/AMA1IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA48B480kAMA1IMA24 (2 Modules Required)N/AMA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA48BC480kAMA1IMA24 (2 Modules Required)N/AMA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA48B1480kAMA1IMA241 (2 Modules Required)N/AMA1IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS2IMA12B120kAMA1IMA12MA1IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS2IMA12BC120kAMA1IMA12MA1IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS2IMA12B1120kAMA1IMA121MA1IMA121MA1IMA121TVS60PCKTVS3DSPHC
TVS2IMA16B160kAMA1IMA16MA1IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS2IMA16BC160kAMA1IMA16MA1IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS2IMA16B1160kAMA1IMA161MA1IMA161MA1IMA161TVS60PCKTVS3DSPHC
TVS2IMA24B240kAMA1IMA24MA1IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS2IMA24BC240kAMA1IMA24MA1IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS2IMA24B1240kAMA1IMA241MA1IMA241MA1IMA241TVS60PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS2IMA32B320kAMA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA32BC320kAMA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA32B1320kAMA1IMA161 (2 Modules Required)MA1IMA161 (2 Modules Required)MA1IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA48B480kAMA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA48BC480kAMA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA48B1480kAMA1IMA241 (2 Modules Required)MA1IMA241 (2 Modules Required)MA1IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS3IMA12B120kAMA1IMA12MA3IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS3IMA12BC120kAMA1IMA12MA3IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS3IMA12B1120kAMA1IMA121MA3IMA121MA1IMA121TVS60PCKTVS3DSPHC
TVS3IMA16B160kAMA1IMA16MA3IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS3IMA16BC160kAMA1IMA16MA3IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS3IMA16B1160kAMA1IMA161MA3IMA161MA1IMA161TVS60PCKTVS3DSPHC
TVS3IMA24B240kAMA1IMA24MA3IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS3IMA24BC240kAMA1IMA24MA3IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS3IMA24B1240kAMA1IMA241MA3IMA241MA1IMA241TVS60PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS3IMA32B320kAMA1IMA16 (2 Modules Required)MA3IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA32BC320kAMA1IMA16 (2 Modules Required)MA3IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA32B1320kAMA1IMA161 (2 Modules Required)MA3IMA161 (2 Modules Required)MA1IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA48B480kAMA1IMA24 (2 Modules Required)MA3IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA48BC480kAMA1IMA24 (2 Modules Required)MA3IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA48B1480kAMA1IMA241 (2 Modules Required)MA3IMA241 (2 Modules Required)MA1IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4IMA12B120kAMA4IMA12MA4IMA12MA4IMA12TVS60PCKTVS3DSPHC
TVS4IMA12BC120kAMA4IMA12MA4IMA12MA4IMA12TVS60PCKTVS3DSPHC
TVS4IMA12B1120kAMA4IMA121MA4IMA121MA4IMA121TVS60PCKTVS3DSPHC
TVS4IMA16B160kAMA4IMA16MA4IMA16MA4IMA16TVS60PCKTVS3DSPHC
TVS4IMA16BC160kAMA4IMA16MA4IMA16MA4IMA16TVS60PCKTVS3DSPHC
TVS4IMA16B1160kAMA4IMA161MA4IMA161MA4IMA161TVS60PCKTVS3DSPHC
TVS4IMA24B240kAMA4IMA24MA4IMA24MA4IMA24TVS60PCKTVS3DSPHC
TVS4IMA24BC240kAMA4IMA24MA4IMA24MA4IMA24TVS60PCKTVS3DSPHC
TVS4IMA24B1240kAMA4IMA241MA4IMA241MA4IMA241TVS60PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4IMA32B320kAMA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA32BC320kAMA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA32B1320kAMA4IMA161 (2 Modules Required)MA4IMA161 (2 Modules Required)MA4IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA48B480kAMA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA48BC480kAMA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA48B1480kAMA4IMA241 (2 Modules Required)MA4IMA241 (2 Modules Required)MA4IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC

Surgelogic Label

To find your SPD part #, locate a white Surgelogic sticker on the interior of your SPD. This can typically be found on the sidewalls or on the door of the SPD. The label will look like the following:

tvss

Schneider Electric USA

Replacement Components for Surgelogic™ QED Switchboard IMA Surge Protective Devices
Issue:
What are the replacement components for QED Switchboard IMA series Surge Protective Devices?

Product Line:
Surge Protective Devices (SPDs)

Environment:
QED Switchboard Type IMA surge protective devices.

Cause:
Replacement or Repair Parts

Resolution:
To determine the correct Replacement parts to purchase for your QED Switchboard Type IMA series Surge Protective Devices (SPDs), see the Replacement Component Selector Table below. An example of a typical product label and catalog number is at the end of this article. 

Replacement Component Matrix
 
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS1IMA12B120kAMA1IMA12N/AMA1IMA12TVS60PCKTVS1DSPHC
TVS1IMA12BC120kAMA1IMA12N/AMA1IMA12TVS60PCKTVS1DSPHC
TVS1IMA12B1120kAMA1IMA121N/AMA1IMA121TVS60PCKTVS1DSPHC
       
TVS1IMA16B160kAMA1IMA16N/AMA1IMA16TVS60PCKTVS1DSPHC
TVS1IMA16BC160kAMA1IMA16N/AMA1IMA16TVS60PCKTVS1DSPHC
TVS1IMA16B1160kAMA1IMA161N/AMA1IMA161TVS60PCKTVS1DSPHC
       
TVS1IMA24B240kAMA1IMA24N/AMA1IMA24TVS60PCKTVS1DSPHC
TVS1IMA24BC240kAMA1IMA24N/AMA1IMA24TVS60PCKTVS1DSPHC
TVS1IMA24B1240kAMA1IMA241N/AMA1IMA241TVS60PCKTVS1DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS1IMA32B320kAMA1IMA16 (2 Modules Required)N/AMA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA32BC320kAMA1IMA16 (2 Modules Required)N/AMA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA32B1320kAMA1IMA161 (2 Modules Required)N/AMA1IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
       
TVS1IMA48B480kAMA1IMA24 (2 Modules Required)N/AMA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA48BC480kAMA1IMA24 (2 Modules Required)N/AMA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS1IMA48B1480kAMA1IMA241 (2 Modules Required)N/AMA1IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS2IMA12B120kAMA1IMA12MA1IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS2IMA12BC120kAMA1IMA12MA1IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS2IMA12B1120kAMA1IMA121MA1IMA121MA1IMA121TVS60PCKTVS3DSPHC
       
TVS2IMA16B160kAMA1IMA16MA1IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS2IMA16BC160kAMA1IMA16MA1IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS2IMA16B1160kAMA1IMA161MA1IMA161MA1IMA161TVS60PCKTVS3DSPHC
       
TVS2IMA24B240kAMA1IMA24MA1IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS2IMA24BC240kAMA1IMA24MA1IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS2IMA24B1240kAMA1IMA241MA1IMA241MA1IMA241TVS60PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS2IMA32B320kAMA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA32BC320kAMA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA32B1320kAMA1IMA161 (2 Modules Required)MA1IMA161 (2 Modules Required)MA1IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
       
TVS2IMA48B480kAMA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA48BC480kAMA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS2IMA48B1480kAMA1IMA241 (2 Modules Required)MA1IMA241 (2 Modules Required)MA1IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS3IMA12B120kAMA1IMA12MA3IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS3IMA12BC120kAMA1IMA12MA3IMA12MA1IMA12TVS60PCKTVS3DSPHC
TVS3IMA12B1120kAMA1IMA121MA3IMA121MA1IMA121TVS60PCKTVS3DSPHC
       
TVS3IMA16B160kAMA1IMA16MA3IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS3IMA16BC160kAMA1IMA16MA3IMA16MA1IMA16TVS60PCKTVS3DSPHC
TVS3IMA16B1160kAMA1IMA161MA3IMA161MA1IMA161TVS60PCKTVS3DSPHC
       
TVS3IMA24B240kAMA1IMA24MA3IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS3IMA24BC240kAMA1IMA24MA3IMA24MA1IMA24TVS60PCKTVS3DSPHC
TVS3IMA24B1240kAMA1IMA241MA3IMA241MA1IMA241TVS60PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS3IMA32B320kAMA1IMA16 (2 Modules Required)MA3IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA32BC320kAMA1IMA16 (2 Modules Required)MA3IMA16 (2 Modules Required)MA1IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA32B1320kAMA1IMA161 (2 Modules Required)MA3IMA161 (2 Modules Required)MA1IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
       
TVS3IMA48B480kAMA1IMA24 (2 Modules Required)MA3IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA48BC480kAMA1IMA24 (2 Modules Required)MA3IMA24 (2 Modules Required)MA1IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS3IMA48B1480kAMA1IMA241 (2 Modules Required)MA3IMA241 (2 Modules Required)MA1IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4IMA12B120kAMA4IMA12MA4IMA12MA4IMA12TVS60PCKTVS3DSPHC
TVS4IMA12BC120kAMA4IMA12MA4IMA12MA4IMA12TVS60PCKTVS3DSPHC
TVS4IMA12B1120kAMA4IMA121MA4IMA121MA4IMA121TVS60PCKTVS3DSPHC
       
TVS4IMA16B160kAMA4IMA16MA4IMA16MA4IMA16TVS60PCKTVS3DSPHC
TVS4IMA16BC160kAMA4IMA16MA4IMA16MA4IMA16TVS60PCKTVS3DSPHC
TVS4IMA16B1160kAMA4IMA161MA4IMA161MA4IMA161TVS60PCKTVS3DSPHC
       
TVS4IMA24B240kAMA4IMA24MA4IMA24MA4IMA24TVS60PCKTVS3DSPHC
TVS4IMA24BC240kAMA4IMA24MA4IMA24MA4IMA24TVS60PCKTVS3DSPHC
TVS4IMA24B1240kAMA4IMA241MA4IMA241MA4IMA241TVS60PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4IMA32B320kAMA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA32BC320kAMA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)MA4IMA16 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA32B1320kAMA4IMA161 (2 Modules Required)MA4IMA161 (2 Modules Required)MA4IMA161 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
       
TVS4IMA48B480kAMA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA48BC480kAMA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)MA4IMA24 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC
TVS4IMA48B1480kAMA4IMA241 (2 Modules Required)MA4IMA241 (2 Modules Required)MA4IMA241 (2 Modules Required)TVS60PCK (2 Kits Required)TVS6DSPHC

Surgelogic Label

To find your SPD part #, locate a white Surgelogic sticker on the interior of your SPD. This can typically be found on the sidewalls or on the door of the SPD. The label will look like the following:

tvss

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.