Can the RealStream be configured so that an alarm triggers a DO to activate a local autodialer?
There is an Auxiliary Alarm Output sensor. If that sensor is enabled and installed on an IO point (DO), the assigned DO will turn on any time there is an active alarm.
It does not turn on for alerts. The system cannot be configured so that a DO will turn ON only if a specific alarm is raised.
For instance you cannot configure it to turn on if the HH alarm is raised, but not turn on if the LL alarm is raised.

Schneider Electric USA

Can the RealStream be configured so that an alarm triggers a DO to activate a local autodialer?
There is an Auxiliary Alarm Output sensor. If that sensor is enabled and installed on an IO point (DO), the assigned DO will turn on any time there is an active alarm.
It does not turn on for alerts. The system cannot be configured so that a DO will turn ON only if a specific alarm is raised.
For instance you cannot configure it to turn on if the HH alarm is raised, but not turn on if the LL alarm is raised.
 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.