{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Why does my M580 or M340 crash after adding a BMXXBE1000 module?

Issue
Can not connect using Unity Pro or Control Expert.

Product line
M580, M340

Resolution
The most common reason for this behavior is an unterminated bus. If the XBE module is installed, it must be fully terminated. This means that it should have both ports connected. The top port of the XBE in the main backplane should have a terminator marked 'A' on it. The bottom port should have an extension cable connected to the top port of the XBE on the expansion backplane. The bottom port of the XBE in the expansion backplane should have a terminator marked 'B' on it. If any of these four ports is disconnected from either the terminator or cable, the CPU will crash. Even if the expanded backplane is powered down, the cables and terminators must remain in place.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Why does my M580 or M340 crash after adding a BMXXBE1000 module?

Issue
Can not connect using Unity Pro or Control Expert.

Product line
M580, M340

Resolution
The most common reason for this behavior is an unterminated bus. If the XBE module is installed, it must be fully terminated. This means that it should have both ports connected. The top port of the XBE in the main backplane should have a terminator marked 'A' on it. The bottom port should have an extension cable connected to the top port of the XBE on the expansion backplane. The bottom port of the XBE in the expansion backplane should have a terminator marked 'B' on it. If any of these four ports is disconnected from either the terminator or cable, the CPU will crash. Even if the expanded backplane is powered down, the cables and terminators must remain in place.

 

If this FAQ did not solve your issue, you can chat with us at  chat with us  or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.