What are the ambient temperature and altitude limits for the Masterpact MTZ?
Issue:
Ambient and Altitude considerations for Masterpact MTZ
Product Line:
Air Circuit Breakers
Resolution:
See attachments for more details.
Ambient and Altitude considerations for Masterpact MTZ
Product Line:
Air Circuit Breakers
Resolution:
Ambient temperature:
- Operating ambient temperatures: -25 C to +70 C
- Shipping and storage temperatures: -40 C to +85 C
- Damp heat: relative humidity 95%, temperature +55 C
- Dry cold temperature tests defined by IEC 60068-2-1
- Dry heat temperature tests defined by IEC 60068-2-2
- Damp heat tests defined by IEC 60068-2-30
See attachments for more details.
Released for:Schneider Electric USA