How to roll back NetBotz firmware.
Issue:
How to roll back NetBotz firmware.
Product Line:
Netbotz
Environment:
NetBotz 3xx, 4xx, and 5xx firmware
Cause:
If for some reason you feel the need to revert back to a previous firmware (BotzWare) revision on a NetBotz appliance, you can not simply use the upgrade feature.
Resolution:
Follow the detailed instructions for the TFTP procedure highlighted in FA176133.
Replace step 1 with the version of BotzWare to which you are looking to downgrade. Older revisions may be available at: www.apc.com/tools/download
Please note that when downgrading, it is suggested that you not keep any of the old configuration and do not use the "rootupgkeep" option in step 17.