Search FAQs
How to program an ATV340 drive for 3-wire control?
Issue:
Setting up ATV340 for 3-wire Control.
Product Line:
ATV340, Altivar 340
Environment:
All
Cause:
N/A
Resolution:
From Main menu,
Go to Complete Settings and press enter.
Go down to Command and Reference and press enter.
Go down to 2/3-wire Control and press enter.
Set for 3-wire control. This will require the enter key(dial) to be pressed for 3 seconds.
In 3-wire control mode, DI1 is normally closed momentary Stop and DI2 is normally open momentary Start.
If DI1 is not made the drive will display NST.
Setting up ATV340 for 3-wire Control.
Product Line:
ATV340, Altivar 340
Environment:
All
Cause:
N/A
Resolution:
From Main menu,
Go to Complete Settings and press enter.
Go down to Command and Reference and press enter.
Go down to 2/3-wire Control and press enter.
Set for 3-wire control. This will require the enter key(dial) to be pressed for 3 seconds.
In 3-wire control mode, DI1 is normally closed momentary Stop and DI2 is normally open momentary Start.
If DI1 is not made the drive will display NST.
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: