{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.

Search FAQs

Can the knockout patterns in load centers, safety switches and metering, be expanded(or cut larger in the field) to accommodate larger conduit sizes?

Issue:
Product Design Features

Product Line:
Load Centers, Safety Switches, Metering

Environment:
Knockout Pattern

Cause:
Application

Resolution:
The knockout patterns in the products should be more than sufficient to accommodate conduit sizes for the wires required to supply the product for its maximum amperage rating and should not be cut or enlarged in the field.

BUT if for some reason a KO pattern needs to be expanded (or Cut larger than the maximum KO size), that will be between the installer and the local code authority. Always check with the local Code BEFORE expanding or cutting knockout patterns larger than what is factory supplied.

Schneider Electric USA

Explore more
Range:
MP Meter-Pak Meter CentersEZ Meter-Pak Meter CentersSolar Disconnect SwitchesNon-Fusible Safety Switches (Heavy Duty)Heavy Duty Safety Switches
Explore more
Range:
MP Meter-Pak Meter CentersEZ Meter-Pak Meter CentersSolar Disconnect SwitchesNon-Fusible Safety Switches (Heavy Duty)Heavy Duty Safety Switches
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.