Issue
Do the M580 Redundant power supplies share the load?
Product line
Modicon M580, Modicon X80
BMXCPS3522, BMXCPS4022
Resolution
The Primary supply supports 100% (or close to 100%) of the load and the Standby 0%.
As far as sizing goes, the nominal draw of both power supplies must be accounted for. In a 24VDC setting, it will be 1.9 A + 1.9 A or 3.8 A
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.