{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
AltivarProcess ATV600, ATV900 Variable speed drive: Identifying Active Configuration in Multi-Configuration or Multi-Motor Setup in the PLC code
To know which configuration is active, read register CNFS (active configuration) at address 8020.
Values returned:
0 = in progress (during changing configuration)
1= config 0 is active
2=config 1 is active
3=config 2 is active
4=config 3 is active

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: