{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What does Unity message "Due to alignment constraint, you have to decrease or increase topological address index of 1 : xxxxxxx" indicate?
Issue
When trying to build a project, the above message appears.

Product line
Unity Pro, Control Expert, Modicon M340, Modicon M580

Resolution
This message means that a double word type variable was created and located to an odd numbered Modbus address. For example if you create a variable Type REAL and locate it to %MW11, you would see this message.
It is suggesting that you either make the address %MW12 or %MW10. The M340 and M580 do not support an ODD address located to a double word variable type.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: