Issue
There are tools for searching and replacing variables either in the Data Editor or from a Variable search. Right clicking on Function blocks in logic after selecting them will allow a wildcard replace of variables on pins. These are cumbersome if a Global effort is underway where we want to search and replace all instances of a variable name whether in sections or the data editor. Is there an option other than these tools?
Product line
Control Expert, Unity Pro
Resolution
- Export the project to a ZEF file.
- Right click on the ZEF file and select 7-ZIP then Open archive. (or simply open it as an archive)
- Right click on the unitpro.xef file from the archive and select Edit (this should launch Notepad)
- Using Notepad's Edit - Search and Replace make the modifications.
- Save the unitpro.xef file. (this should update the unitpro.xef that is in the ZEF)
- Open the ZEF with Control Expert and you should see your changes.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for:Schneider Electric USA
Issue
There are tools for searching and replacing variables either in the Data Editor or from a Variable search. Right clicking on Function blocks in logic after selecting them will allow a wildcard replace of variables on pins. These are cumbersome if a Global effort is underway where we want to search and replace all instances of a variable name whether in sections or the data editor. Is there an option other than these tools?
Product line
Control Expert, Unity Pro
Resolution
- Export the project to a ZEF file.
- Right click on the ZEF file and select 7-ZIP then Open archive. (or simply open it as an archive)
- Right click on the unitpro.xef file from the archive and select Edit (this should launch Notepad)
- Using Notepad's Edit - Search and Replace make the modifications.
- Save the unitpro.xef file. (this should update the unitpro.xef that is in the ZEF)
- Open the ZEF with Control Expert and you should see your changes.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: