Hot to Install a Driver in ClearSCADA?
To install a driver in ClearSCADA follow the following steps:
- Shut down the server.
- Use the ClearSCADA installation wizard.
- Click Next
- Click Modify
- Expand the server and select the driver you want to install press Next and follow the steps to finish the installation
Any icon that displays a red cross indicates a component that will not be installed.
- Restart the Server after finishing the installation.
- Repeat the above steps on the other servers on your system. (On a Hot-Standby system, once you have installed the new driver(s) on a standby server, bring that server back online and synchronize it with the main server. Repeat the above steps with any other standby servers, then perform a manual changeover to upgrade one of the standby servers to main. Following this, install the driver(s) on the machine that was previously main, then bring that server back online.)