{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
How do I erase the program in the internal memory of a TSX Micro PLC?

Article available in these languages: Japanese


Issue:
Erasing the internal memory of a TSX Micro PLC.


Product Line:
TSX Micro, PL7 Micro


Resolution:
In some cases, it may be useful to totally erase the contents of the internal RAM or FLASH EPROM of the TSX37 PLC. To erase the PLC program, during a power-up keep the DIAG button pressed for a minimum of 10 seconds. After this time the ERR light will flash and the RUN light will be off. This indicates no program is in the PLC memory.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: