{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Making Online Logic Changes in Remote Connect

This article describes how to perform online changes to logic in Remote Connect.

1. Ensure that you are online with the SCADAPack x70 controller

2. In the logic editor, make your changes.  Once finished, the dialog below will appear.  Click ‘Yes’

(Notice the bottom right corner reads, “MEM BUILT” before you click ‘Yes’.  After you click ‘Yes’ it reads, “NOT BUILT”.




cid:image002.jpg@01D525C9.9F332100

cid:image004.jpg@01D525C9.9F332100





3. Next, from the top menu click on Build | Build Changes








4. A ‘List of modified sections’ dialog will appear.  Click ‘Yes’




cid:image023.jpg@01D525C9.9F332100




5. The changes should now build (i.e. you’ll see a green bar graph moving left to right).  Once the build finishes, an ‘Online Modification’ dialog will appear.  Click ‘OK’




cid:image024.jpg@01D525C9.9F332100




6. You’ll now need to go back to Remote Connect where (on the ‘Online Diags’ dialog) an ‘Online Modification’ dialog will appear.  Click on ‘Write Source Now’




cid:image027.jpg@01D525C9.9F332100



Schneider Electric USA

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.