Can a Delta Primary Transformer be connected to a 3 phase 4 wire Wye source?

Article available in these languages: Spanish

Issue:
Connecting a Wye source to a Delta primary

Product Line:
Square D Transformers

Environment:
Transformer Wiring

Resolution:
A Wye Source can be connected to the Primary side of a Delta transformer. The neutral would have to be left out and the 3 hot legs would have to be connected on the Primary taps based on the wiring diagram provided for the transformer.

Schneider Electric USA

Can a Delta Primary Transformer be connected to a 3 phase 4 wire Wye source?

Article available in these languages: Spanish

Issue:
Connecting a Wye source to a Delta primary

Product Line:
Square D Transformers

Environment:
Transformer Wiring

Resolution:
A Wye Source can be connected to the Primary side of a Delta transformer. The neutral would have to be left out and the 3 hot legs would have to be connected on the Primary taps based on the wiring diagram provided for the transformer.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.