How to configure Event Watcher to trigger on Sag/Swell events only
Product Line
Power Monitoring Expert

Environment
Event Watcher

Resolution
Event Watcher must be configured to use a template the only references Sag/Swell Events.

To create the template follow the steps below:
  1. Open Event Watcher by going to Management Console, select Tools >> Reporting Configuration >> Event Watcher Manager
  2. Select the Templates tab
  3. Click New
  4. Give the alarm a name such as PQ Events - Sag/Swell
  5. If desired, give the alarm a description
  6. Choose 'Select From Event Log'
  7. Select Sag/Swell {0.EN_US}|1 Disturbance Start SS1 DistState Disturbance
  1. Press OK and then apply to save the template

Configure Event watcher to use the Sag/Swell template by using the following steps.
  1. Inside of Event Watcher choose the Event Watchers tab.
  2. Select New in the top right
  3. Give the alarm a name
  4. Select the Sag/Swell template created above
  5. If desired, give the alarm a description
  6. Select the device(s) that the alarm will apply to
  1. Press OK
For steps on how to create a report subscription using this event trigger see FA300069.

Schneider Electric USA

How to configure Event Watcher to trigger on Sag/Swell events only
Product Line
Power Monitoring Expert

Environment
Event Watcher

Resolution
Event Watcher must be configured to use a template the only references Sag/Swell Events.

To create the template follow the steps below:
  1. Open Event Watcher by going to Management Console, select Tools >> Reporting Configuration >> Event Watcher Manager
  2. Select the Templates tab
  3. Click New
  4. Give the alarm a name such as PQ Events - Sag/Swell
  5. If desired, give the alarm a description
  6. Choose 'Select From Event Log'
  7. Select Sag/Swell {0.EN_US}|1 Disturbance Start SS1 DistState Disturbance
  1. Press OK and then apply to save the template

Configure Event watcher to use the Sag/Swell template by using the following steps.
  1. Inside of Event Watcher choose the Event Watchers tab.
  2. Select New in the top right
  3. Give the alarm a name
  4. Select the Sag/Swell template created above
  5. If desired, give the alarm a description
  6. Select the device(s) that the alarm will apply to
  1. Press OK
For steps on how to create a report subscription using this event trigger see FA300069.
 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.