Problem:

I need to create a hot-standby pair. I currently have a single standalone server running a Geo SCADA application. What do I need to know about in advance?


Solution:

Below are some items to consider before creating a hot-standby pair:

1. The standby server will need a similar license to the current standalone machine. It should have the same features, drivers and number of points. The number of ViewX or WebX clients may vary between the servers. In addition, both the current standalone server and the future standby server licenses must have the redundancy option included.

2. The licenses need to be applied to both servers prior to the reconfiguration.

3. Both servers need to have the same version of Geo SCADA installed along with the same drivers and driver extensions.

4. Both servers should have similar server configuration applied.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.