How can we help you today?
What is the general rule in recommending shielded and non-shielded motor cables for drives?
Issue:
Drive installation with shielded or unshielded cable?
Product Line:
Altivar Machines
Environment:
All models
Cause:
N/A
Resolution:
If you do not have metallic conduit ( i.e. non-metallic piping or trays ), shielded cable is recommended so that noise is not radiated. According to EMC directives, shielded cable is required.
Drive installation with shielded or unshielded cable?
Product Line:
Altivar Machines
Environment:
All models
Cause:
N/A
Resolution:
If you do not have metallic conduit ( i.e. non-metallic piping or trays ), shielded cable is recommended so that noise is not radiated. According to EMC directives, shielded cable is required.
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: