What does the endurance test consist of that a UL489 circuit breaker must pass?

Article available in these languages: Spanish

Issue:
What is the endurance rating for the thermal magnetic breakers?

Product Line:
Circuit Breakers

Resolution:
Circuit breakers are tested to UL489 and CSA 22.2. For endurance, both thermal-magnetic and electronic circuit breakers must successfully complete the number of operations shown in the below table.
  • Power factor shall be 0.75 to 0.80 lagging.
  • Starting in the open position, the breaker is closed, then opened (this counts as one operation)
  • The Full Load Operations Test is done at rated current and voltage
  • The No Load Operations Test is done following the Full Load Test
Frame Size in AmperesFull Load OperationsNo Load Operations
0-1006,0004,000
101-2254,0004,000
226-6001,0005,000
601-8005003,000
801-25005002,000
2501-40004001,000

NOTES:
Circuit breakers are not tested until they fail, so the maximum number of operations is not known.
Environmental factors affect the life of a breaker, so the number of test operations in the table should not be interpreted as a guaranteed number in actual use.

Schneider Electric USA

What does the endurance test consist of that a UL489 circuit breaker must pass?

Article available in these languages: Spanish

Issue:
What is the endurance rating for the thermal magnetic breakers?

Product Line:
Circuit Breakers

Resolution:
Circuit breakers are tested to UL489 and CSA 22.2. For endurance, both thermal-magnetic and electronic circuit breakers must successfully complete the number of operations shown in the below table.
  • Power factor shall be 0.75 to 0.80 lagging.
  • Starting in the open position, the breaker is closed, then opened (this counts as one operation)
  • The Full Load Operations Test is done at rated current and voltage
  • The No Load Operations Test is done following the Full Load Test
Frame Size in AmperesFull Load OperationsNo Load Operations
0-1006,0004,000
101-2254,0004,000
226-6001,0005,000
601-8005003,000
801-25005002,000
2501-40004001,000

NOTES:
Circuit breakers are not tested until they fail, so the maximum number of operations is not known.
Environmental factors affect the life of a breaker, so the number of test operations in the table should not be interpreted as a guaranteed number in actual use.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.