Issue:
Lug torque requirements for QOU breakers
Product Line:
Miniature Circuit Breakers
Resolution:
45 lb. in. for 10-70 amp one and two pole, and 10-60 amp three pole.
50 lb. in. for 80-100 amp one pole, 80-125 amp two pole, and 70-100 amp three pole.
Lug torque requirements for QOU breakers
Product Line:
Miniature Circuit Breakers
Resolution:
45 lb. in. for 10-70 amp one and two pole, and 10-60 amp three pole.
50 lb. in. for 80-100 amp one pole, 80-125 amp two pole, and 70-100 amp three pole.
Released for:Schneider Electric USA

