1999 NEC 450-21(b) states ``Individual dry-type transformers of more than 112.5 kVA rating shall be installed in a transformer room of fire-resistant construction. ...`` How does this apply to low voltage transformers made by Square D?
Issue:
Clarification of National Electrical Code section NEC 450-21(b)
Product Line:
LV Transformers
Environment:
Applies to Ventilated and Non-Ventilated SquareD/Schneider Electric Transformers with a Class 220 insulation system
Cause:
Code Section NEC450-21(b) may call for clarification in some installation situations
Resolution:
This is not a concern to SquareD/Schneider Electric  low voltage dry type transformers with enclosures as we comply with 1999 NEC 450-21(b) Exception No. 2, which states ``Transformers with Class 155 or higher insulation systems and completely enclosed except for ventilating openings.``

SquareD/Scheider Electric Ventilated and Non Ventilated low voltage dry type Transformers utilize a Class 220 insulation system, which is higher than a Class 155.

The previous versions of code section 450-21(b) used to reference 80?C rise as the differentiation point. The intent for that was to require units with Class 150 insulation to be in the fire-rated room, and one aspect of a Class 150 insulation system transformer is a standard 80?C rise. This created unnecessary cost for those using a Watchdog 80C rise transformer which utilizes a Class 220 insulation system. The change in the code was done to clarify the intent of this section.


Schneider Electric USA

1999 NEC 450-21(b) states ``Individual dry-type transformers of more than 112.5 kVA rating shall be installed in a transformer room of fire-resistant construction. ...`` How does this apply to low voltage transformers made by Square D?
Issue:
Clarification of National Electrical Code section NEC 450-21(b)
 
Product Line:
LV Transformers
 
Environment:
Applies to Ventilated and Non-Ventilated SquareD/Schneider Electric Transformers with a Class 220 insulation system
 
Cause:
Code Section NEC450-21(b) may call for clarification in some installation situations
 
Resolution:
This is not a concern to SquareD/Schneider Electric  low voltage dry type transformers with enclosures as we comply with 1999 NEC 450-21(b) Exception No. 2, which states ``Transformers with Class 155 or higher insulation systems and completely enclosed except for ventilating openings.``

SquareD/Scheider Electric Ventilated and Non Ventilated low voltage dry type Transformers utilize a Class 220 insulation system, which is higher than a Class 155.

The previous versions of code section 450-21(b) used to reference 80?C rise as the differentiation point. The intent for that was to require units with Class 150 insulation to be in the fire-rated room, and one aspect of a Class 150 insulation system transformer is a standard 80?C rise. This created unnecessary cost for those using a Watchdog 80C rise transformer which utilizes a Class 220 insulation system. The change in the code was done to clarify the intent of this section.


 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.