Can you install a QO-GFI, QO-CAFI, QO-DF, or QO-EPD breaker in a QO24L70F, QO24L70S, or QO24L70RB load center?
Issue:
Application

Product Line:
QO LC

Resolution:
Yes. When using an electronic branch breaker, the QO24L70F, S, or RB has adequate wire bending space for a maximum #10 AWG wire. This will restrict the QO-GFI and QO-EPD breakers to a maximum of 30 amperes.