{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Needs to add lugs for a bigger wire size for 400SN Neutral Assembly
Issue:
Are optional lugs available for the 400SN neutral assembly?

Product Line:
Panelboards

Environment:
ILine Panelboards

Resolution:
Yes, optional lugs are available for the 400SN neutral assembly. The standard lug provided on the neutral assembly will accept (1) #1 AWG - 600 kcmil or (2) #1 AWG - 250 kcmil CU or AL conductors. Optional lugs include: AL400LH7 for (1) 350 -750 kcmil CU or AL conductor: CU400LA for (1) #1 AWG - 600 kcmil or (2) #1 AWG - 250 kcmil CU only conductors. The optional lug kits contain one lug. Two kits would be required to change both the incoming and outgoing neutral lugs.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: