What is the difference between AFI and GFI circuit breakers?
Issue:
Product Design Features
Product Line:
Miniature Circuit Breakers
Resolution:
The AFI is a UL listed circuit breaker designed to mitigate the effects of arcing faults. It is required by UL to protect against arcs between current carrying conductors above 75 A (Square D AFI protects from arcs above 50 A), and may trip on leakage to ground with a minimum threshold of 30 to 50 mA.
The GFI is a circuit breaker UL listed for interrupting the circuit when more than 6 mA of ground fault leakage is detected.

Schneider Electric USA

What is the difference between AFI and GFI circuit breakers?
Issue:
Product Design Features
 
Product Line:
Miniature Circuit Breakers
 
Resolution:
The AFI is a UL listed circuit breaker designed to mitigate the effects of arcing faults. It is required by UL to protect against arcs between current carrying conductors above 75 A (Square D AFI protects from arcs above 50 A), and may trip on leakage to ground with a minimum threshold of 30 to 50 mA.
 
The GFI is a circuit breaker UL listed for interrupting the circuit when more than 6 mA of ground fault leakage is detected.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.