{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Smartlink SIB - Why Cumulative Registers Drop Off after a Power Cycle ?

Product Line

Smartlink SIB - A9XMZA08

Environment
Standalone product.
Connected with Power Monitoring Expert

Issue
Customers that have some Smartlink connected to Power Monitoring Expert complained that some Smartlink registers dropped to an older value after a power cycle of the product.
image.png

Cause of Issue
This is a known issue related to internal memory for devices that have Firmware lower than v2.4.6
Smartlink with Firmware v2.4.2 or lower are concerned.

Resolution
Download EcoStruxure Power Commission v2.20 (EPC)
Connect your Smartlink SIB directly to your EPC.
Launch the Smartlink FW upgrade to v2.4.6 with EPC.

Schneider Electric USA

Smartlink SIB - Why Cumulative Registers Drop Off after a Power Cycle ?

Product Line

Smartlink SIB - A9XMZA08

Environment
Standalone product.
Connected with Power Monitoring Expert

Issue
Customers that have some Smartlink connected to Power Monitoring Expert complained that some Smartlink registers dropped to an older value after a power cycle of the product.
image.png

Cause of Issue
This is a known issue related to internal memory for devices that have Firmware lower than v2.4.6
Smartlink with Firmware v2.4.2 or lower are concerned.

Resolution
Download EcoStruxure Power Commission v2.20 (EPC)
Connect your Smartlink SIB directly to your EPC.
Launch the Smartlink FW upgrade to v2.4.6 with EPC.

Schneider Electric USA

Explore more
Product:
Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Explore more
Product:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.