What size solar/AC battery can be backfed in the Energy Center?
Issue:
How large of a solar or AC battery can be backfed in the Energy Center?

Product Line:
Energy Center

Resolution:
The 120% rule allows for the maximum solar/AC battery backfeed for the top section to be 160 A total. However, to avoid submain circuit breaker nuisance tripping, limit the solar/AC backfed breaker to 120 A.

An additional 120 A can be added to the bottom section per the 120% rule, so the total is 240 A backfed. Installer will need to check with AHJ and the homeowner’s utility for the maximum interconnection agreement.

Schneider Electric USA

What size solar/AC battery can be backfed in the Energy Center?
Issue:
How large of a solar or AC battery can be backfed in the Energy Center?

Product Line:
Energy Center

Resolution:
The 120% rule allows for the maximum solar/AC battery backfeed for the top section to be 160 A total. However, to avoid submain circuit breaker nuisance tripping, limit the solar/AC backfed breaker to 120 A.

An additional 120 A can be added to the bottom section per the 120% rule, so the total is 240 A backfed. Installer will need to check with AHJ and the homeowner’s utility for the maximum interconnection agreement.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.