Why are my modified parameters not saving when I change the part number in an ATV320 SoMove configuration file
Issue:
Customer is using the Modify button in a saved ATV320 project file to change the part number of the drive, but all settings are reset to factory default.

Product Line:
ATV320 and SoMove

Environment:
Offline programming

Cause:
Software

Resolution:
This issue has been reported to the software team.  At this time there is no scheduled update.
This appears to occur only when modifying a previously existing project file.
In order to modify the part number for a specific file where this happens:
  1. Use Import/Export from the File menu in SoMove to Export the .PSX file to  a .CFG file.
  2. Close the project
  3. Use Import/Export from the File Menu in SoMove to import the new .CFG file, select ATV320, and then select the new ATV320 part number.
The motor nameplate information may be reset if the values do not fall within the adjustment range of the new drive part number but all other modified settings should remain.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.