Should the long time rating plug be removed before insulation and dielectric withstand test in MVS Micrologic?
It is not necessary to remove long time rating plug in Micrologic ET2/ETA2/ ET5S/ETA5S/ ET6G/ETA6G before before insulation and dielectric withstand test .
It is absolutely necessary to remove long time rating plug in Micrologic ETV2I/ ETV5S/ ETV6G before insulation and dielectric withstand test