Search FAQs
What is the In-rush current of the HMISTW6/HMIST6?
On Schneider Electric website (www.se.com), the inrush current of different HMIs is provided with the unit A (Ampere): For example, the inrush current of the HMISTW6400 is 30 A. This comparatively high inrush current makes our customers wonder.
The goal of this article is to provide the inrush current with the unit: A²*s like our competitors.
This article is applicable to the following products:
HMISTW6, HMIST6
Find below the inrush current of the HMISTW6/HMIST6 with unit A²*s:
The goal of this article is to provide the inrush current with the unit: A²*s like our competitors.
This article is applicable to the following products:
HMISTW6, HMIST6
Find below the inrush current of the HMISTW6/HMIST6 with unit A²*s:
Series | Display size | In-rush current |
Harmony ST6 Harmony STW6 | 4w”/7” w | 0.2 A²*s |
10” w/12” w/ 15” w | 0.6 A²*s |
Released for:Schneider Electric USA
Explore more
Product:
Explore more
Product: