{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Can an XDSE SPD be connect to a branch breaker with an existing load?

Issue:

XDSE SPD connection to a branch breaker.

Product Line:

Surge Protection Devices

Environment:

XDSE Surgelogic SPD

Resolution:

"Since the current drawn by the XDSE device during normal operation is negligible, the XDSE device can be connected to a dedicated, separate branch circuit or connected to a suitable existing branch circuit."

page 7, XDSE User Guide 9501 07/2018

It can but they will have to use a breaker that accepts multiple conductors per lug and also has the wire range that complies with the wire range that XDSEs has which is stated on its handout (XDSE Handout), #8 to #10 AWG. This will assure that the wire leads of the SPD device are still protected.

Schneider Electric USA

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: