Can the MMS kits for Powerpact P and R frame breakers be used on Masterpact NW?
Issue:
Will the Arc Flash Reduction switch MMS work on a Masterpact NW and NT breaker?
Product Line:
Masterpact NW and NT
Resolution:
The Powerpact MMS kits LV429659 for 120 Vac or LV429658 for 24 Vdc will work on the Masterpact breaker. Trip units with A, P, or H functions are required and MMS is not compatible with ZSI.
Will the Arc Flash Reduction switch MMS work on a Masterpact NW and NT breaker?
Product Line:
Masterpact NW and NT
Resolution:
The Powerpact MMS kits LV429659 for 120 Vac or LV429658 for 24 Vdc will work on the Masterpact breaker. Trip units with A, P, or H functions are required and MMS is not compatible with ZSI.