Is it normal to have continuity between the phases when the transformer is not yet energized?

Article available in these languages: Spanish

Issue:

Low voltage transformer having continuity between phases when not energized

Product Line:

LV Transformers

Environment:

All Low voltage transformers, EE, EX, EXN

Resolution:

Continuity is normal between the phases of the primary and secondary sides of the transformer even if they're not energized (H1 and H2 or H2 and H4 etc) or (X1 and X2 or X2 and X3 etc). What's not normal is having continuity on the primary and secondary sides (H1 and X1 or H2 and X2 etc).

Schneider Electric USA

Is it normal to have continuity between the phases when the transformer is not yet energized?

Article available in these languages: Spanish

Issue:

Low voltage transformer having continuity between phases when not energized

 

Product Line:

LV Transformers

 

Environment:

All Low voltage transformers, EE, EX, EXN

 

Resolution:

 

Continuity is normal between the phases of the primary and secondary sides of the transformer even if they're not energized (H1 and H2 or H2 and H4 etc) or (X1 and X2 or X2 and X3 etc). What's not normal is having continuity on the primary and secondary sides (H1 and X1 or H2 and X2 etc).

 

 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.