Can I use the “Transfer Test” of the ATS to start the generator without switching load?
No.  The “Transfer Test” feature of the ATS is designed to simulate loss of preferred power and initiate load transfer to the alternate power.  Hence the term “Transfer” Test.

Transfer Test Buttons and Selector Switch

Schneider Electric USA

Can I use the “Transfer Test” of the ATS to start the generator without switching load?
No.  The “Transfer Test” feature of the ATS is designed to simulate loss of preferred power and initiate load transfer to the alternate power.  Hence the term “Transfer” Test.

Transfer Test Buttons and Selector Switch
 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.