How must I configure OPC UA communications when an IPSEC tunnel is configured?
In the case where secured OPC UA client connect to the BMENUA server and IPSEC tunnels are activated to the clients, by default the OPC UA connections will pass inside the tunnel. For the best performances, we recommend configuring the product in order to pass these OPC UA connections outside the tunnel. This can be done as following:
  • ADD a new FORWARDING rule,
  • Select OPC UA protocol,
  • Inbound interface CONTROL PORT or BOTH,
  • uncheck IPSEC in use in order to force OPC UA traffic to pass outside the IPSEC tunnel

Product Line

BMENUA0100 version 2.01

Environment

Windows, EADM

Schneider Electric USA

How must I configure OPC UA communications when an IPSEC tunnel is configured?
In the case where secured OPC UA client connect to the BMENUA server and IPSEC tunnels are activated to the clients, by default the OPC UA connections will pass inside the tunnel. For the best performances, we recommend configuring the product in order to pass these OPC UA connections outside the tunnel. This can be done as following:
  • ADD a new FORWARDING rule,
  • Select OPC UA protocol,
  • Inbound interface CONTROL PORT or BOTH,
  • uncheck IPSEC in use in order to force OPC UA traffic to pass outside the IPSEC tunnel  

Product Line

BMENUA0100 version 2.01

Environment

Windows, EADM
 

Schneider Electric USA

Explore more
Product:
Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Explore more
Product:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.