Product Line:
QO Load Center
Environment:
Enclosed Molded Case Switch and Enclosed Circuit Breaker Devices
Cause:
What is the difference between the enclosure that comes with the QO200TR and the QO2TR?
Resolution:
The interiors for these two are different. The QO200TR is tested and listed as a molded case switch with no overcurrent protection. It comes with a QO200 factory installed. While the QO2TR is tested and listed as a circuit breaker enclosure in which customer can install a molded case QO circuit breaker. The enclosures may look the same but the interior supplied on both are different. And the interiors for these two are not interchangeable or swapped.