{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What would cause the error "Topological address index is not valid" in EcoStruxure Control Expert after a build?
Issue:
"Topological address index is not valid" error in EcoStruxure Control Expert after a build


Product Line:
EcoStruxure Control Expert


Resolution:
The error occur when a variable is assigned to a memory object that is not allocated in the processor configuration. In the example below, the variable has an array length of 26 EBOOLs starting at %M500 to %M525. The processor memory management is configured for only 512 Ebools(%M). This is not enough to satisfy the array length. To clear the error, simply increase the %M to a number greater than 525 and rebuild the project.


image

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: