{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
How to run Process Drives with a small or no motor

Issue:

How to run Process Drives with a small or no motor


Product Line:

ATV630/ ATV930

Environment:

Open Circuit

Cause:

n/a

Resolution:

Go to Complete Settings, Then select Motor Parameters, scroll down to Motor Control Type- set to U/F VC 5 pts then go to Error/Warning Handling- Output Phase Loss- set to Function Inactive.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: