Recommendations and Clarifications for SPD Circuit Breakers and Wire Sizing.
Circuit Breaker and Wire Sizes for Surge Protection Devices

Schneider Electric Square D Surgelogic and ASCO 400 series surge protective devices (SPDs) incorporate individually fused and thermally protected metal oxide varistors (MOVs). This feature provides superior withstand capability for systems with unstable power, without compromising transient clamping performance. The component level fusing also allows the surge protector to be directly connected to the electrical bus without external overcurrent protection. When connecting via a breaker, which acts as a service disconnect, consult local electrical codes to select the appropriate size based upon the wire gauge to be used. Based upon National Electric Code (NEC), factory recommendations are listed above. For technical support contact SPDTAG@se.com (800) 577-7353.

Schneider Electric USA

Recommendations and Clarifications for SPD Circuit Breakers and Wire Sizing.
Circuit Breaker and Wire Sizes for Surge Protection Devices

Schneider Electric Square D Surgelogic and ASCO 400 series surge protective devices (SPDs) incorporate individually fused and thermally protected metal oxide varistors (MOVs). This feature provides superior withstand capability for systems with unstable power, without compromising transient clamping performance. The component level fusing also allows the surge protector to be directly connected to the electrical bus without external overcurrent protection. When connecting via a breaker, which acts as a service disconnect, consult local electrical codes to select the appropriate size based upon the wire gauge to be used. Based upon National Electric Code (NEC), factory recommendations are listed above. For technical support contact SPDTAG@se.com (800) 577-7353.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.