Export of the configuration to a .xhw file is not available.
The Control Expert help indicates that the M580 configuration can be exported to a .xhw file.
p1


If you try to export the configuration , the only selection available is a .zhw file.
p2


To resolve the issue:
  • Export the configuration to the .zhw fle.  (The  zhw file is a zipped file).
  • Open the exported zhw file with 7zip.
  • Extract the .xhw file from the zip file.
p3