{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
After upgrade Nutanix Cluster Check (NCC) 4.6.2 PowerChute Network Shutdown cannot power down AHV hosts.

Issue:
After upgrade to (Nutanix Cluster Check) NCC 4.6.2 the AHV root account gets locked out if the password is changed. This will prevent PowerChute from shutting down AHV hosts.

Product:
PowerChute Network Shutdown

Environment:
Nutanix AHV host, NCC 4.6.2

Cause:
The AHV root account gets locked.

Solution:
Upgrade NCC to version 4.6.3. Please refer to the following Nutanix Knowledge Base article - https://portal.nutanix.com/page/documents/kbs/details?targetId=kA07V000000H4dZSAS

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: