When trying to change the NodeName of a controller inside EcoStruxure Machine Expert I'm unable to do it and receive the following image:
This is a bug currently being worked on version 2.1 and previous ones of EcoStruxure Machine Expert.
However, this FAQ presents a workaround to change the NodeName of your controller by following these steps:
1) Inside ESME, click on "Tools" tab
2) Select "Options ..."
3) Select "Device editor" in the left menu
4) In the "Communication page" section, select "Classic mode".
5) Proceed to change the NodeName in the new Communication Page.
6) [Optional] If you prefer the previous Communication Page layout, you can change it back to the traditional view (repeat steps from 1 to 4, in step 4 select "Controller selection mode" in the "Communication Page").
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for:Schneider Electric USA
When trying to change the NodeName of a controller inside EcoStruxure Machine Expert I'm unable to do it and receive the following image:
This is a bug currently being worked on version 2.1 and previous ones of EcoStruxure Machine Expert.
However, this FAQ presents a workaround to change the NodeName of your controller by following these steps:
1) Inside ESME, click on "Tools" tab
2) Select "Options ..."
3) Select "Device editor" in the left menu
4) In the "Communication page" section, select "Classic mode".
5) Proceed to change the NodeName in the new Communication Page.
6) [Optional] If you prefer the previous Communication Page layout, you can change it back to the traditional view (repeat steps from 1 to 4, in step 4 select "Controller selection mode" in the "Communication Page").
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.